Addressable Fire Alarm System

Addresable Fire Alarm Control Panel
รายละเอียดสินค้า

FireNET Denver Door
Analog Addressable Fire Alarm Control Panel  | Data Sheet

    STANDARD FEATURES

    • Analog design using Hochiki's advanced DCP protocol for fast and robust communication
    • UL 864 9th edition Listed
    • Up to 127 sensors & modules, plus 127 analog sounder bases, for a total of 254 points possible per loop
    • Uses standard wire, no shielded or twisted pair required on SLC loops
    • Supports Class B (style 4) and Class A (style 6 or 7) SLC loops
    • 4 on board Class B (style Y) NAC circuits rated at 2.5 Amps each
    • Programmable sensitivity levels per device & automatic day/ night sensitivity modes
    • Automatic daily calibration & drift compensation routine
    • Large 8-line x 40-character LCD display (320 char.)
    • 2 or 4 loop versions (800 addresses/sub-addr. max.)
    • Dual RS-485 bus for panel network
    • 2 built-in RS-232 interfaces for programming via a PC and serial printer interface
    • 5 on board programmable Form C relays rated at 1 amp at 30VDC (Fire1, Fire2, trouble, supervisory, aux.)
    • 500mA of auxiliary power available rated at 24 VDC
    • Loop Explorer Windows® configuration utility
    • 500 network wide software zones
    • Network Capability of up to 64 panels
    • RS485 slave bus for expansion - up to 32 FN-4127-IO boards or up to 15 FN-LCD-S serial annunciators and up to 17 FN-4127-IO boards
    • Auto-learn feature
    • Built in help and alarm information screens
    • Fire Drill test function
    • Walk Test function
    • Alarm Verification feature
    • FireNET is UL listed for Central Station Service, Remote Station Service and Proprietary Service
    • Operates on 120VAC or 240VAC input voltage
    • Powerful & versatile Cause & Effect programming (up to 500 maximum, network wide) including: Cause & Effect action, Disable function configuration, Test mode configuration


    Addresable Fire Alarm Control Panel
    รายละเอียดสินค้า

    FireNET (9th Edition)
    Analog Addressable Fire Alarm Control Panel  | Data Sheet

    STANDARD FEATURES

    • UL 864 9th edition approved
    • Analog design using Hochiki's advanced DCP protocol for fast and robust communication
    • Up to 127 sensors & modules, plus 127 analog sounder bases, for a total of 254 points possible per loop
    • Uses standard wire, no shielded or twisted pair required on SLC loops
    • Supports Class B (style 4) and Class A (style 6 or 7) SLC loops
    • 4 on board Class B (style Y) NAC circuits rated at 2.5 Amp each
    • Programmable sensitivity levels per device & automatic day/night sensitivity modes
    • Automatic daily calibration & drift compensation routine
    • Large 8-line x 40-character LCD display (320 char.)
    • 2 or 4 loop versions (800 addresses/sub-addr. max.)
    • Dual RS-485 bus for panel network
    • 2 built-in RS-232 interfaces for programming via a PC and serial printer interface
    • 5 on board programmable Form C relays rated at 1 amp at 30VDC (Fire1, Fire2, trouble, supervisory, aux.)
    • 500mA of auxiliary power available rated at 24 VDC
    • Loop Explorer Windows® configuration utility
    • *500 network wide software zones
    • Network Capability of up to 64 panels
    • RS485 slave bus for expansion - up to 32 FN-4127-IO boards or up to 15 FN-LCD-S serial annunciators and up to 16 FN-4127-IO boards
    • Auto-learn feature
    • Built in help and alarm information screens
    • Fire Drill test function
    • Walk Test function
    • Alarm Verification feature
    • FireNET is UL listed for Central Station Service when used with the Bosch D9068 contact dialer
    • Powerful & versatile Cause & Effect programming (up to 500 maximum, network wide) including: *Cause & Effect action, *Disable function configuration, *Test mode configuration


    Analogue -Alarm Contro Panel
    รายละเอียดสินค้า

    HOCHIKI : UL PRODUCTS - Analogue - Alarm Control Panel Accessories 

    FNP-LED

    Data Sheet

    FNP-LED (MIMIC LED Display)

    STANDARD FEATURES:
    • Available in Red and Charcoal Gray
    • Up to 504 LED's can be controlled with FireNET Plus Panel
    • Available in 3 different size enclosures
    • LED's comes in 3 different colors: Red, Green, or Yellow
    • FNP-LED can be easily upgraded onsite with minimal cost and effort  

    FN-LCD-N_9th_Edition

    Data Sheet

    FN-LCD-N (Network Annunciator)

    STANDARD FEATURES:
    • UL 864 9th edition approved
    • 320 character liquid crystal display (8 line x 40 character)
    • Dual RS-485 ports for primary fire network
    • 2 built-in RS-232 interfaces for programming via a PC and serial printer interface
    • True Peer-to-Peer network annunciation

    FN-LCD-S_9th_Edition

    Data Sheet

    FN-LCD-S (Serial Annunciator)

    STANDARD FEATURES:

    • UL 864 9th edition approved
    • Large 320 character liquid crystal display (8 line x 40 character) 
    • Resides on the FireNET slave RS-485 lin

     

    FN-ACC-R_C

    Data Sheet

    FN-ACC-R/C (Battery/Accessories Enclousure)

    STANDARD FEATURES:
    • Designed to provide a method to properly store backup batteries for the FireNET and FireNET Plus panels
    • The enclosure can also be used to mount 16 Channel I/O Boards
    • The battery enclosure comes in two colors Red (FN-ACC-R) & Charcoal (FN-ACC-C), and comes with a keylock

     

     

    TCF-142-M-ST

    Data Sheet

    Instruction

    TCF-142-M-ST (Fibre Optic Module)

    STANDARD FEATURES:
    • Capability to network FireNET™, FireNET Plus, and Network Annunciator using fiber optic cables
    • Extends RS-485 transmission up to 3.1 miles
    • Protects against electrical interface and chemical corrosion
    • No special programming required
    • UL 864 9th Edition Liste

    FN-4127-SLC

    Data Sheet

    FN-4127-SLC (Dual Loop Expander Card for FireNet)

    STANDARD FEATURES:
    • Adds two SLC loops to a two loop FireNET control panel
    • Each SLC loop is capable of 127 sensors/modules, plus 127 analog sounder bases, for a potential total of 254 addresses per loop (127+127 per loop)
    • FN-4127-SLC can be added at the factory or installed in the field
    • Supports Class A and B wiring methods per NFPA72 Styles 4, 6, and 7 (with isolators)
    • Fully supervised & power limited SLC loops
    • Supports Hochiki's DCP (Digital. Communication Protocol) loop protocol
    • Same functionality as built-in SLC loops of FireNET control panel
    • One SLC expander (maximum) may be added per FireNET control panel
    • Each SLC loop is completely independent and autonomous
    • Uses standard wire, no shielded or twisted pair required on SLC loop

    FNP-1127-SLC

    Data Sheet

    FNP-1127-SLC (Single Loop Expander Card for FireNet Plus)

    STANDARD FEATURES:
    • Adds one SLC loop to the FireNET Plus (FNP-1127E series) control panel
    • The SLC loop is capable of 127 sensors/modules, plus 127 analog sounder bases, for a potential total of 254 addresses
    • The FireNET Plus 1127E control panel supports one FNP-1127-SLC, for a total of two SLC loops per panel
    • Supports Class A and B wiring methods per NFPA 72 Styles 4, 6, and 7 (Style 7 requires isolators)
    • Fully supervised & power limited SLC loop
    • Supports Hochiki's DCP (Digital Communication Protocol)
    • Same functionality as built-in loop of FireNET Plus control panel
    • Uses standard wire; shielded/twisted pair is not required on SLC loops

    FN-4127-NIC

    Data Sheet

    FN-4127-NIC (Dual RS-485 Network Interface Card)

    STANDARD FEATURES:
    • Allows for the expansion of up to 64 panels on a FireNET system
    • Enables information to be transmitted between control panels
    • Network protocol designed for tolerance to interference and data corruption
    • Each card configured to a unique address through use of a dipswitch
    • Transmission distance of up to 4,000 ft.
    • Uses standard type Belden cable suitable for RS-485 applications
    • Simple 2-wire loop connection
    • Flexible configuration options
    • Network wide Cause & Effect logic
    • Fully secure against short or open conditions

    FN-4127-IO

    Data Sheet

    FN-4127-IO (16 Channel Input/Output Board)

    STANDARD FEATURES:
    • 16 channels of input/output points
    • 32 I/O boards per FireNET panel (512 channels of input/output points)
    • Each channel configurable as input or output point
    • Inputs are opto-isolated non-supervised pulldown type triggered by
    • Outputs are open collector transistor pulldown type (100mA max each) that provide
    • Simple 4 wire connection to control panel (2 for power, 2 for data)
    • All inputs/outputs can be assigned to global functions, any event category, and used in network wide Cause & Effect logic
    • Can be mounted locally within control panel enclosure or remotely via FN-ACC accessory enclosure up to 4000ft from the panel
    • Each I/O board has a unique address 1-32 (set via DIP switch) on the I/O Comms Bus
    • Input/Outputs are for secondary use, not for primary fire initiation inputs or notification outputs
    • Two LED's are provided for communication status

    FireNET_Graphix_Software

    Data Sheet

    GUS Series (FireNET Graphix Alarm Management Software)

    STANDARD FEATURES:
    • Choice of text, graphic and event list display when event occurs
    • Versatile event analysis
    • Total history archive
    • Easy to program
    • Secure system
    • Cost effective compared to other systems
    • Simple to use
    • Unlimited map linking
    • Display and control for multiple panels
    • Event history can be viewed, filtered and exported to text or HTML documents


    Manual Pull Station Addressable
    รายละเอียดสินค้า

    DCP-AMS
    Addressable Manual Pull Station |Data Sheet

    STANDARD FEATURES
    • Addressable integrated design
    • All metal construction
    • Single and dual action models available
    • Extremely easy to operate
    • Bi-colored status LED indicates Standby and Alarm conditions
    • Address is programmable in EEPROM
    • Address can be programmed when installed
    • Key lock or hex key lock models available
    • Terminals accept up to 14AWG wire
    • Surface mount back box available


    Smoke Detector Photoelectric sensor
    รายละเอียดสินค้า

    HOCHIKI : UL PRODUCTS - Analogue - Sensors

    ALN-V

    Data Sheet

    ALN-V (Photoelectric Smoke Sensor)

    STANDARD FEATURES:

    • Low profile - Only 2.00" high, including base
    • Simple and reliable device addressing
    • Automatic compensation for sensor contamination
    • Built-in fire test feature
    • Uses the noise-immune Digital Communication Protocol (DCP), which utilizes interrupts for fast
    response to fires
    • Two built-in power/alarm LEDs
    • Programmble non-polling LEDs
    • Non-directional smoke chamber
    • Vandal resistant security locking feature
    • Removable smoke labyrinth for cleaning or replacement

     

    ATJ-EA

    Data Sheet

    ATJ-EA (Rate of Raise Heat Sensor)

    STANDARD FEATURES:

    • Low profile - only 2" high, including base
    • Simple and reliable device addressing method
    • Uses the noise immune Digital Communication Protocol (DCP),which utilizes interrupts for fast response to fires
    • Rate of Rise temperature threshold = 15°F/Min (determined by panel)
    • Adjustable threshold temperature = 135°F - 190°F (determined by panel)

    ACC-V

    Data Sheet

    ACC-V (Multi-Criteria Sensor)

    STANDARD FEATURES:

    • Low profile - Only 2.00" high, including base
    • Simple and reliable device addressing
    • Automatic compensation for sensor contamination
    • Built-in fire test feature
    • Uses the noise-immune Digital Communication Protocol
    (DCP), which utilizes interrupts for fast response to fires
    • Two built-in power/alarm LEDs
    • Programmable non-polling LEDs
    • Non-directional smoke chamber
    • Vandal resistant security locking feature
    • Removable smoke labyrinth for cleaning or replacement



    AMC2188 Addressable Manual call point
    รายละเอียดสินค้า
    AW-AMC2188 Addressable Manual call point
    AW-AMC2188 Addressable Manual call point is a mated product of the 2100 series fire alarm control panels.
      
    Product Overview : The AW -AMC2188 addressable manual call point (manual call point for short) is mainly designed to be used with an intelligent two-bus control panel. If it is pressed after a fire is manually confirmed, an alarm signal may be sent to a fire alarm control panel which will, after receiving the alarm signal, display the coded address and the equipment status of the manual call point.

    When the manual call point is operating normally, the red indicator will blink; when there is a fire alarm, it will remain lit. The manual call point supports electronic coding and has a built-in fire telephone jack and a PHONE indicator, making its engineering application convenient.
     
    Features:
    1. It can realize complete electronic coding and in situ rewriting with help of a coder.
    2. Designed with an upper cover and a lower cover, it can be installed, debugged and maintained conveniently.
    3. It is designed with a two-wire fire telephone jack and is therefore more applicable to engineering application.
    4. Designed with passive output contacts, it can control other external equipment directly through an intermediate relay.
    5. The pressing sheet on the manual call point will not get crushed after it is pressed, but can be reset by a special tool, so it can be used repeatedly.
      Parameters: 
    1. Operating voltage: 24V (pulse modulation);
    2. Operating current: <300uA (in the monitoring status); <2mA (in the action status);
    3. Output contact: Normally open contact; capacity: 0.1A/30VDC;
    4. Weight: About 120g;
    5. Wiring method: nonpolar two-bus system (L1, L2);
    6. Operating environment: Indoor, temperature: -10℃~+50℃; relative humidity: ≤95% (40℃±2℃, without condensation);
    7. Coding method: It can realize online coding with the help of a coder and without the necessity of disassembling the bus (however, the equipment must be powered off). Address codes 1 to 324 are available for selection;
    8. Telephone jack: Two-wire fire telephone jack (equipped with a standard Ф6.3 single-track audio connector);
    9. Starting part: A plastic pressing sheet that may be used repeatedly. It can be manually reset with a special tool after being pressed;
    10. Starting mode: Press the pressing sheet manually;
    11. Indicator: The red ALARM indicator will blink in the inspection status or remain lit in the alarm status; the PHONE indicator will blink when a fire telephone loop is connected, otherwise it will be out;
    12. Matched host machine: fire alarm control panel (such as AW-AFP2188, AW-AFP2100).
       


    ATD2188 Addressable Heat Detector
    รายละเอียดสินค้า
    AW-ATD2188 Addressable Heat Detector
    AW-ATD2188 addressable heat detector is a mated product of the 2188/2100 series fire alarm control panels. 
     
    AW-ATD2188 addressable heat detector (Detector hereunder) is a mated product of the 2188/2100 series fire alarm control panels. It uses a two-bus work mode. With an internal microprocessor, it supports electronic coding.

    The detector realizes real-time acquisition of the in situ temperature data and sends back the data to a fire alarm control panel. It can also receive and execute the control commands given by a fire alarm control panel. When in a routing inspection, the detector indicator will blink.

    When there is a fire in the monitored area and the temperature has reached the alarm threshold, the fire alarm control panel will confirm a fire alarm according to the received message sent from the detector, and the detector indicator will light at the same time to indicate a fire alarm.

    The detector is suitable for such industrial and civil buildings that have a great deal of heat when fire takes place, such as kitchens, boiler rooms, generator rooms, drying workshops and smoking rooms and is not suitable for places with a great deal of smoke but little heat.
     
    Features:
     
    1. It can realize electronic coding and rewrite the address via coder in situ.
    1. Within a single-chip microcomputer, it can realize real-time data acquisition and processing, realize a curve tracing for the field situation.
    1. It has a temperature compensation function and a sensor fault detection function (fault reporting to fire alarm control panel).
    2. Non-polarity, two-bus connection that ensures convenient installation and maintenance.
    1. Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained conveniently.

    Parameters: 

    1. Executive standard: GB4715-2005;
    2. Operating voltage: 24V (pulse modulation);
    3. Operating current: <300uA (monitoring status) or <1.5mA (alarm status);
    4. Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm status;
    5. Weight: about 47g;
    6. Product class: A2;
    7. External dimensions: diameter: 100mm, height: 56mm (with the base);
    8. Wiring method: non-polarity two-bus system (L1, L2);
    9. Operating environment: Indoor, temperature: 10℃~+50℃; relative humidity: ≤95% (40℃±2℃, without condensation);
    10. Coding mode: It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for selection;
    11. Installation height: ≤8m;
    12. Protection area: about 60m². For details, see related provisions in GB50116-98 Code for Design of Automatic Fire Alarm System;
    13. Matched host machine: fire alarm control panel (such as AW-AFP2188, AW-AFP2100).


     


    ASD2188 Addressable Smoke Detector
    รายละเอียดสินค้า
    AW-ASD2188 Addressable Smoke Detector
    AW-ASD2188 Addressable smoke detector is a kind of photoelectric smoke detector.
     
    AW-ASD2188 Addressable smoke detector (Detector hereunder) is a kind of photoelectric smoke detector. With an internal microprocessor, it supports electronic coding and is accessed through a compatible fire alarm control panel of AW-AFP2188 via a two-wire bus.

    The detector realizes real-time acquisition of the in situ smoke concentration data and sends back the data to a fire alarm control panel. It can also receive and execute the control commands given by a fire alarm control panel.

    The detector is suitable for such industrial and civil buildings that have a great deal of smoke during fires but no smoke under normal circumstances, such as restaurants, hotels, teaching buildings, office buildings, computer rooms, communication machine rooms, libraries and archives. It is not suitable for places with a great deal of retained dust and water mist, places where steam and/or oil mist may be generated and places with retained smoke under normal

      Characteristics:

     

    1. It can realize electronic coding and rewrite the address via coder in situ.
    2. Within a single-chip microcomputer, it can process the sampling data in real-time, save the latest 144 historical data and realize a curve tracing for the field situation.
    3. It has a temperature, humidity and dust accumulation drift compensation function and a sensor fault detection function (fault reporting to fire alarm control panel).
    4. Non-polarity, two-bus connection that ensures convenient installation and maintenance.
    5. Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained conveniently.
     
    Parameter: 
    1. Executive standard: GB4715-2005;
    2. Operating voltage: 24V (pulse modulation);
    3. Operating current: £¼300uA (monitoring status) or £¼1.5mA (alarm status);
    4. Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm status;
    5. Weight: about 70g;
    6. External dimensions: diameter: 100mm, height: 55mm (with the base);
    7. Wiring method: non-polarity two-bus system (L1, L2);
    8. Operating environment: Indoor, temperature: 10℃~+55℃; relative humidity: ≤95% (40℃±2℃, without condensation);
    9. Coding mode: It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for selection;
    10. Installation height: ≤12m;
    11. Protection area: about 60m 2. For details, see related provisions in GB50116-98 Code for Design of Automatic Fire Alarm System;
    12. Matched host machine: fire alarm control panel (such as AW-AFP2188, AW-AFP2100).
       


    AFP2100 Addressable Fire Alarm Control Panel
    รายละเอียดสินค้า
    AFP2100 Addressable Fire Alarm Control Panel
     PRODUCT OVERVIEW : 
    The AW-AFP2100 series control panel (linkage type) (fire alarm control panel) is a new generation product launched by ASENWARE. In order to adapt to the needs of engineering design, the fire alarm control panel is designed with a linkage control function that enables it to be flexibly used with other related products from ASENWARE to form a fire alarm and linkage integrated control system. It is particularly suitable for applications in large and medium-sized fire alarm and linkage integrated control systems.

    The AW-AFP2100 series addressable control panel is a dual wire analog bus system. It can replace the conventional fire alarm system to save 50% or more cables.

    The AW-AFP2100 series addressable control panel is an advanced, perfect and reliable system, which is designed for big porjects, has been used in many countries
     
    Parameter: 

    Capacity:
    1. Each loop card has 2 loops, with 324 addresses as alarm/control points of each loop, the capacity of each loop card is 324*2=648(addresses);
    2. Each wall mounted AW-AFP2100 panel can be installed maximum 3 loop cards, the maxium capacity is 648*3=1944(addresses). Over 1944 addresses, use the cabinet panel, the cabinet panel can be installed maxium 40 loop cards, the maximum capacity is 648*40=25920(addresses);
    3. Peer-to-peer with max.20 AW-AFP2100 panels, the maxium system capacity: 25920*20=518400(addresses);
    Maximum simultaneous alarm of each host:
    • Fire alarm: 500;
    • Trouble: 500;
    • Feedback: 500.
    Operating evironment:
    Temperature-10℃~+55℃
    Humidity≤95%, 40℃,non-condensing
    AC PowerAC220V, 50HZ,3A
    DC PowerDC24V,7A


    AFP2189 Addressable Fire Alarm Control Panel
    รายละเอียดสินค้า
    AW-AFP2189 Addressable Fire Alarm Control Panel
    AW-AFP2189 fire alarm control panel is a new generation of fire alarm control panel launched. In order to meet the engineering design demand, the control unit is provided with both linkage and control...
     
     PRODUCT OVERVIEW : 
    AW-AFP2189 fire alarm control panel (hereinafter referred to fire control unit) is a new generation of fire alarm control panel launched. In order to meet the engineering design demand, the control unit is provided with both linkage and control functions. It can support uses of other related products of the Company to form an integrated alarm and linkage control system, which is perfectly suitable for the application of small and medium-sized fire alarm and firefighting and linkage integrated control system.

    The fire alarm linkage control system is widely used in small and medium-sized firefighting engineering, such as high-grade office building, residential community, department store, gymnasium, exhibition room, library, workshop, supermarket and hotels.  
     
    System features

    1. Adopts the latest generation of high-speed microprocessor. Data processing rate and data storage capacity reach 100-fold and 1000-fold increase, respectively, compared to traditional technologies
    2. AW-AFP2189 is provided with 4.3" color display screen (LCD), with a display resolution of 430×272.
    3. The operation interface imitates Windows menus and window interfaces and is almost the same as the computer operating and using habits, thus facilitates the learning.
    4. Operation and control are flexible and convenient through the standard USB-interfaced computer keyboard and mouse + the panel buttons are used as field programming devices.
    5. T9 pinyin input method is provided and texts can be input easily and freely.
    6. Use smart U disk (optional), which can be used to copy or restore setup file and historical file of the system, thus facilitating the system maintenance.
    7. It adopts the non-polarity two-bus intelligent alarm linkage pattern and can connect 324 intelligent detectors or intelligent modules at most. The addresses of module detectors can be mix-programmed (optional 1-324)
    8. It supports interconnection of 20 AW-AFP2189 control units and the maximum system capacity after networking reaches 20×324=6480 (alarm point)
    9. The maximum capacity of linkage control unit of a single equipment: 10 points
    10. The system has the function of recording operation history: 1000 pieces of historical fire alarms, historical requests, historical feedbacks, historical faults and historical operations, respectively
    11. The user may customize the equipment type, which can facilitate the system integration
    12. It has the modular manual single-point start/stop functions, which can facilitate field debugging and testing
    13. It has the single-point detector/module testing function, the detector working status and test data are clearly displayed
    14. The system is provided with a dedicated mini-printer as standard, which is used to print various operating statuses of the system immediately
    15. It can be accessed with area indicating panels, building indicating panels and floor indicating panels, which will extend display information of the control unit to corridor and other locations
    16. It can be connected with PC to achieve city networking.
    17. The system carries out the hierarchy management of multi-level users and the users of different levels are granted with corresponding operating system permissions, which is convenient for system management
    18. It is possible to update the system on the field or remotely to ensure the system operates stably and reliably
    19. Standards: GB 4717-2005 Fire Alarm Control Unit
    GB 16806-2006 Automatic Control System for Fire Protection
     
    Power supply
    Mains power supply: AC 220V±20%/50Hz or DC24V;
    Backup power supply: DC24V maintenance-free battery BAT12V/5AH

    System operating environment
    Ambient temperature: -10℃~+55℃
    Ambient humidity: ≤95% (40℃±2℃, no condensation)